Supply Ability : 100000 Piece/Pieces per Month
Price : Get Latest Price
Packaging Details : packed in carton
Delivery Time : WITHIN 15 DAYS
Port : NINGBO OR SHANGHAI
Payment Terms : T/T,Western Union
MOQ : 100 Pint/Pints
Place of Origin : Zhejiang
Brand Name : CNLB
color : black
Model Number : TCJCTG/600A
CURRENT : 600A
Category : Other Wiring Accessories
-
--
rated current:600A
rated voltage:15kV
1. 15KV/600A
2. deadbreak Bushing
3. Integral Deadbreak
4. cable joints
5. with KEMA report
The RU YTGZ-15/600 Integral Deadreak Bushing( cable joints)-combines the advantages of reliable integral design with the operating features required for three-phase switching. The bushing is designed for pad mounted transformers, switchgear and other apparatus fliled with transformer oil, or an approved equivalent. It eliminates the insert-to-well interface present in bushing well and insert primary terminations.
-
The Bushing is molded with high quality insulating material. When mated with comparably rated products, it provides a fully shielded, submersible and separable connection for deadbreak operation.
-
The-RU YTGZ-15/600 Integral Bushing includes two kinds. Type A is used in oil-insulated apparatus and type B is suitable for the air-insulated devices.
-
Interchangeability
-
All-RU Power System 600A Integral Deadbreak Bushing conform to the electrical,
mechanical and dimensional requirements of ANSI/IEEE Standard 386. The Integral
Deadbreak Bushing can be used on any comparably rated connector interface that
also meets the requirements of this standard.
-
Electrical Characteristics:
Voltage Rating and Characteristics |
|
Description |
kv |
Standard Voltage Class |
15 |
Max Rating Phase to phase |
14.4 |
Max Phase to ground |
8.3 |
AC 50 Hz 1 minute Withstand |
42 |
DC 15 minute Withstand |
53 |
BIL and Full Wave Crest |
95 |
15kv Partial Discharge |
≤10PC |
Current Ratings and Characteristics |
|
Description |
Amperes |
Continuous |
600A |
24 hours overhead |
1000A |
Short time |
50kA rms symmetrical for 0.3s 20kA rms symmetrical for 4.0s |
Electrical Characteristics are in accordance with or exceed GB/T 12706.4-2002, ANSI/IEE 386-1995, IEC 60502-4:1997 |
Cable Joints 600A Integral Deadbreak Bushing Images |